116 HAWTHORNE

IN REVIEW
SWIMMING POOL

Status mismatch

This permit has 9 inspection(s) on record but its status is IN REVIEW — not ISSUED. Inspections should only be performed on issued permits. Update the status if this permit has been issued.

Permit Timeline

⬤ In Review 8/21/2026
Issued
MOISTURE BARRIER 05/19/2026 PASS
MOISTURE BARRIER 06/17/2026 PASS
ROUGH BUILDING 08/03/2026 C&R
ROUGH BUILDING 08/14/2026 C&R
ROUGH BUILDING 08/24/2026 PASS
PLUMBING 08/27/2026 PASS
INSULATION 08/27/2026 PASS
POOL BASKET 09/03/2026 PASS
+1 More
Permit Finaled
Certificate Issued

Project Information

Edmunds #

—

MC #

MC2026-464

Issued Date

—

Finaled Date

—

Owner

—

Owner Address

—

Contractor

—

Project Type

SWIMMING POOL

Description

PUBLIC SWIMMING POOL - RECTANGULAR OUTDOOR GUNITE POOL, 74' X 28', MINIMUM DEPTH 2'-9", MAXIMUM DEPTH 5'-0", AREA 2,072 SQ. FT., VOLUME 52,037 GALLONS, AT THE PRESERVE AT FOXRUN

Technical Details

Construction Type

—

Occupancy Group

—

Occupant Load

—

Square Footage

2072

Zoning

—

Sprinklers

—

APN

—

Limitations

—

Inspection History

Date Type Inspector Result Notes
09/03/2026 POOL BASKET Tyler Adams PASS —
09/03/2026 ROUGH ELE BON P Tyler Adams PASS —
08/27/2026 PLUMBING Tyler Adams PASS —
08/27/2026 INSULATION Tyler Adams PASS —
08/24/2026 ROUGH BUILDING Tyler Adams PASS —
08/14/2026 ROUGH BUILDING Tyler Adams CORRECT AND RECALL - MISSING FOUR DOUBLE HANGERS IN HALLWAY AROUND ATTIC PULL DOWN - NAIL ON ROUND BOXES NEED TO BE SECURED WITH THE NAILS ATTACHED TO THE BOX NOT SCREWS THROUGH THE BOX - FLOOR OUTLET BOXES ARE NOT CEMENTED TO CONDUIT, COUPLINGS ARE JUST SLID OVER BOXES
08/03/2026 ROUGH BUILDING Tyler Adams CORRECT AND RECALL - fir out wall at low volt panel to maintain r value? Or relocate to an uninsulated wall - nail on round boxes in ceiling are installed with sheetrock rock screws through the box, the need to be installed as designed - bond all metal boxes - pancake boxes are over box fill with two cable penetrations - insulate all 3/4 hot waterlines - fir out walls at electrical panels to maintain r value - sheathing behind left electrical panel not fastened to a stud at all - KO seal needed in 2” insider opening bottom of right panel - bond to UFER - bond to gas line - disconnect in back left mechanical closet is a surface mounted disconnect not a recessed mounted disconnect - stub out for urinal needs to be sweated to bracket to keep it from moving in the bracket and causing pin holes down the line - missing nail guard over waterline to middle toilet in men’s restroom - missing four double hangers in ceiling of hallway to restrooms - connections at floor outlets need to be made with appropriate fittings not seal tite and tape
06/17/2026 MOISTURE BARRIER Tyler Adams PASS —
05/19/2026 MOISTURE BARRIER Tyler Adams PASS —