Permit Timeline
In Review
11/19/2025
Issued
10/08/2026
T-POLE
06/22/2026
PASS
ELECTRICAL
07/01/2026
PASS
MOISTURE BARRIER
07/13/2026
PASS
ROUGH BUILDING
07/30/2026
C&R
ROUGH BUILDING
08/18/2026
C&R
PLUMBING
08/18/2026
C&R
FINAL
08/26/2026
C&R
COMBINATION ROUGH
09/16/2026
PASS
+2 More
Permit Finaled
Certificate Issued
Project Information
Edmunds #
—
MC #
MC2026-277
Issued Date
10/08/2026
Finaled Date
—
Owner
I-READY HOMES & DEVELOPMENT LLC
Owner Address
6132 RIVEROAK TERR, ATLANTA, GA 30349
Contractor
METRO PAL CONTRACTORS. LLC
Project Type
NEW SINGLE FAMILY RESIDENTIAL
Description
NEW SFR
Technical Details
Construction Type
—
Occupancy Group
—
Occupant Load
—
Square Footage
2200
Zoning
—
Sprinklers
—
APN
F10 015
Limitations
—
Inspection History
| Date | Type | Inspector | Result | Notes |
|---|---|---|---|---|
| 10/8/2026 | FINAL | TYLER ADAMS | CORRECT AND RECALL | - condenser unit 2 has a nameplate mac breaker size of 15 amps, a 20 amp is installed - pop off for water heater needs to terminate between 18” and 1.5” above finished grade - smoke detector not allowed in garage per NFPA 72 - door from garage needs to be rated - need to see passing blower door certificate - seal corners of master shower - caulk toilets in place - island outlet not installed, required per ga state electrical amendment as of jan1 2026 - lights not installed on kitchen wall and back porch - outlet not installed over fireplace in living room |
| 09/22/2026 | INSULATION | Tyler Adams | PASS | — |
| 09/16/2026 | COMBINATION ROUGH | Tyler Adams | PASS | — |
| 08/26/2026 | FINAL | Tyler Adams | CORRECT AND RECALL | - MISSING ANCHORS ALL AROUND SUN ROOM - FIR OUT WALL AT ELECTRICAL PANEL TO MAINTAIN R-VALUE - UFER CONNECTION NEEDS TO BE ACCESSIBLE - MISSING HANGERS AT ATTIC PULL DOWN - ANCHORS MISSING NUTS AND WASHERS BY GARAGE POSTS - NO ANCHORS IN BACK WALL OF MASTER BEDROOM - ANCHORS IN MASTER BATHROOM MISSING NUTS AND WASHERS - MISSING ANCHORS BEHIND FIREPLACE BOX - ANCHORS MISSING NUTS AND WASHERS IN LIVING ROOM - RE-INSPECTION FEE WILL BE APPLIED |
| 08/18/2026 | ROUGH BUILDING | Kyle Golberg | CORRECT AND RECALL | PREVIOUS CORRECTIONS NOT MADe |
| 08/18/2026 | PLUMBING | Kyle Golberg | CORRECT AND RECALL | — |
| 07/30/2026 | ROUGH BUILDING | Tyler Adams | CORRECT AND RECALL | - ANCHORS REQUIRED WITH IN 12 INCHES OF ALL BREAKS AND JOINTS IN EXTERIOR SILL PLATE - FIR OUT WALL AT ELECTRICAL PANEL TO MAINTAIN R-VALUE - UFER CONNECTION NEEDS TO BE ACCESSIBLE - MISSING HANGERS AT ATTIC PULL DOWN - MISSING NAIL GUARD OVER POP OFF DRAIN THROUGH STUD TO EXTERIOR - NO PRESSURE ON WATERLINES - VENT BATHROOM EXHAUST FANS TO EXTERIOR - HVAC HAS NOT BEEN ROUGHED - MISSING ANCHORS ALL THE WAY AROUND BACK PORCH SUN ROOM |
| 07/13/2026 | MOISTURE BARRIER | Tyler Adams | PASS | — |
| 07/01/2026 | ELECTRICAL | Tyler Adams | PASS | — |
| 06/22/2026 | T-POLE | Tyler Adams | PASS | — |