Permit Timeline
In Review
10/30/2025
Issued
COMBO ROUGH (BMEP)
06/17/2026
C&R
ROUGH BUILDING
07/01/2026
C&R
ROUGH BUILDING
07/21/2026
PASS
INSULATION
07/21/2026
PASS
Permit Finaled
Certificate Issued
Project Information
Edmunds #
P-151125
MC #
MC2026-269
Issued Date
—
Finaled Date
—
Owner
ARTHUR FARR
Owner Address
220 FLINT ST, FORSYTH, GA 31029
Contractor
ARTHUR FARR
Project Type
NEW SINGLE FAMILY RESIDENTIAL
Description
NEW SFR
Technical Details
Construction Type
—
Occupancy Group
—
Occupant Load
—
Square Footage
1200
Zoning
—
Sprinklers
—
APN
031 006
Limitations
—
Inspection History
| Date | Type | Inspector | Result | Notes |
|---|---|---|---|---|
| 07/21/2026 | ROUGH BUILDING | Tyler Adams | PASS | — |
| 07/21/2026 | INSULATION | Tyler Adams | PASS | — |
| 07/01/2026 | ROUGH BUILDING | Tyler Adams | CORRECT AND RECALL | 1. NAIL GUARDS NEEDED OVER PLUMBING THROUGH FRAMING MEMBERS, WHERE WITH IN 1.5 INCHS OF OUTSIDE EDGE OF FRAMING MEMBERS 2. PLUMBING VENT NEEDS TO EXTEND TO EXTERIOR 3. BATHROOM EXHAUST FAN NEEDS TO BE VENTED TO EXTERIOR |
| 06/17/2026 | COMBO ROUGH (BMEP) | Tyler Adams | CORRECT AND RECALL | - BOND ALL METAL BOXES - SECURE ALL CABLES TO FRAMING MEMBERS - GROUND SCREW ON LEFT SWITCH FOR BATHROOM IS NOT TIGHTENED - JUNCTION BOX COVER MISSING FOR CAN LIGHT IN BATHROOM - PLUMBING NOT ROUGHED - SEAL UNUSED HOLE IN DISCONNECT BETWEEN WALLS - DRAFT BLOCKING NEEDED BETWEEN WALLS AND ATTIC - DO NOT SEE A SMOKE DETECTOR ROUGHED - DO NOT SEE ATTIC ACCESS - ARC FAULT AND GROUND FAULT REQUIREMENTS WILL NEED TO BE MET AT FINAL |