381 RUM CREEK RD

FINALED
NEW SINGLE FAMILY RESIDENTIAL

Permit Timeline

In Review 3/23/2026
Issued 09/15/2026
MOISTURE BARRIER 05/18/2026 PASS
COMBINATION ROUGH 05/18/2026 C&R
COMBINATION ROUGH 05/22/2026 C&P
INSULATION 06/03/2026 PASS
PERMANENT SERVICE 07/07/2026 PASS
FINAL 09/04/2026 C&R
FINAL 09/10/2026 PASS
Permit Finaled 9/10/2026
Certificate Issued 10/21/2026

Project Information

Edmunds #

P-510326

MC #

MC2026-127

Issued Date

09/15/2026

Finaled Date

9/10/2026

Owner

BRANDO & JOHN STRICKLAND

Owner Address

381 RUM CREEK RD, FORSYTH, GA 31029

Contractor

MCNEAL BROS, LLC

Project Type

NEW SINGLE FAMILY RESIDENTIAL

Description

NEW SFR

Technical Details

Construction Type

V-B

Occupancy Group

R-3

Occupant Load

N/A

Square Footage

6218

Zoning

A-R

Sprinklers

NO

APN

111 014

Limitations

NONE

Inspection History

Date Type Inspector Result Notes
09/10/2026 FINAL Tyler Adams PASS —
09/04/2026 FINAL Tyler Adams CORRECT AND RECALL - cable to well needs to be buried and stubbed up to disconnect panel in conduit - label disconnect panel - emergency service disconnect stickers needed on service disconnects - remove form board from behind condensers - label ac disconnects in relation to their breakers - seal holes in siding to left of back door from garage - condensers need to have breakers installed that are no larger than the max breaker size on the name plate, all three appear to be wrong - water heaters have not been turned on to test hot water - anti tilt device no installed on oven - bath gfci outlet is dead short - window in second floor front bathroom should be tempered - need to see passing blower door door certificate
07/07/2026 PERMANENT SERVICE Tyler Adams PASS —
06/03/2026 INSULATION Tyler Adams PASS —
05/22/2026 COMBINATION ROUGH Tyler Adams CORRECT AND PROCEED - MISSING WINDOWS - MISSING HANGERS AT ATTIC PULL DOWN - NEED THIMBLE ON FIREPLACE FLUR THROUGH FIREBREAK
05/18/2026 MOISTURE BARRIER Tyler Adams PASS —
05/18/2026 COMBINATION ROUGH Tyler Adams CORRECT AND RECALL - extend portal straps to top plate middle garage door - no pressure on waterlines - multiple windows not installed - waterline to icemaker box ran outside of wall - insulate, waterlines and exterior walls - secure half inch waterline in ceiling to hose bib off back of master bedroom from master bathroom -missing hangers at attic pull down in master closet - no insulation behind moisture barrier behind tubs on exterior walls the second floor - window in front second floor bathroom needs to be tempered - light boxes in second floor common area need to be fan rated - smoke detector in second floor common area needs to be moved further than 36 inches away from the potential ceiling fan in center of room - frame mechanical chase in second floor closet - plumbing vent flashing not installed on roof - no water on second floor tubs and drain - fire break required in fireplace chase