Permit Timeline
In Review
3/23/2026
Issued
09/15/2026
MOISTURE BARRIER
05/18/2026
PASS
COMBINATION ROUGH
05/18/2026
C&R
COMBINATION ROUGH
05/22/2026
C&P
INSULATION
06/03/2026
PASS
PERMANENT SERVICE
07/07/2026
PASS
FINAL
09/04/2026
C&R
FINAL
09/10/2026
PASS
Permit Finaled
9/10/2026
Certificate Issued
10/21/2026
Project Information
Edmunds #
P-510326
MC #
MC2026-127
Issued Date
09/15/2026
Finaled Date
9/10/2026
Owner
BRANDO & JOHN STRICKLAND
Owner Address
381 RUM CREEK RD, FORSYTH, GA 31029
Contractor
MCNEAL BROS, LLC
Project Type
NEW SINGLE FAMILY RESIDENTIAL
Description
NEW SFR
Technical Details
Construction Type
V-B
Occupancy Group
R-3
Occupant Load
N/A
Square Footage
6218
Zoning
A-R
Sprinklers
NO
APN
111 014
Limitations
NONE
Inspection History
| Date | Type | Inspector | Result | Notes |
|---|---|---|---|---|
| 09/10/2026 | FINAL | Tyler Adams | PASS | — |
| 09/04/2026 | FINAL | Tyler Adams | CORRECT AND RECALL | - cable to well needs to be buried and stubbed up to disconnect panel in conduit - label disconnect panel - emergency service disconnect stickers needed on service disconnects - remove form board from behind condensers - label ac disconnects in relation to their breakers - seal holes in siding to left of back door from garage - condensers need to have breakers installed that are no larger than the max breaker size on the name plate, all three appear to be wrong - water heaters have not been turned on to test hot water - anti tilt device no installed on oven - bath gfci outlet is dead short - window in second floor front bathroom should be tempered - need to see passing blower door door certificate |
| 07/07/2026 | PERMANENT SERVICE | Tyler Adams | PASS | — |
| 06/03/2026 | INSULATION | Tyler Adams | PASS | — |
| 05/22/2026 | COMBINATION ROUGH | Tyler Adams | CORRECT AND PROCEED | - MISSING WINDOWS - MISSING HANGERS AT ATTIC PULL DOWN - NEED THIMBLE ON FIREPLACE FLUR THROUGH FIREBREAK |
| 05/18/2026 | MOISTURE BARRIER | Tyler Adams | PASS | — |
| 05/18/2026 | COMBINATION ROUGH | Tyler Adams | CORRECT AND RECALL | - extend portal straps to top plate middle garage door - no pressure on waterlines - multiple windows not installed - waterline to icemaker box ran outside of wall - insulate, waterlines and exterior walls - secure half inch waterline in ceiling to hose bib off back of master bedroom from master bathroom -missing hangers at attic pull down in master closet - no insulation behind moisture barrier behind tubs on exterior walls the second floor - window in front second floor bathroom needs to be tempered - light boxes in second floor common area need to be fan rated - smoke detector in second floor common area needs to be moved further than 36 inches away from the potential ceiling fan in center of room - frame mechanical chase in second floor closet - plumbing vent flashing not installed on roof - no water on second floor tubs and drain - fire break required in fireplace chase |