Permit Timeline
In Review
3/23/2026
Issued
3/23/2026
INSULATION
05/15/2026
PASS
PERMANENT POWER
05/22/2026
PASS
FINAL
07/21/2026
C&R
FINAL
07/24/2026
PASS
Permit Finaled
7/24/2026
Certificate Issued
10/26/2026
Project Information
Edmunds #
P-480326
MC #
MC2026-126
Issued Date
3/23/2026
Finaled Date
7/24/2026
Owner
JOSHUA MADDOX
Owner Address
91 BASS RD APT 238, WARNER ROBINS, GA
Contractor
JOSHUA MADDOX
Project Type
NEW SINGLE FAMILY RESIDENTIAL
Description
NEW SFR
Technical Details
Construction Type
V-B
Occupancy Group
R-3
Occupant Load
N/A
Square Footage
2640
Zoning
R-1
Sprinklers
NO
APN
014A023
Limitations
NONE
Inspection History
| Date | Type | Inspector | Result | Notes |
|---|---|---|---|---|
| 07/24/2026 | FINAL | Tyler Adams | PASS | — |
| 07/21/2026 | FINAL | Tyler Adams | CORRECT AND RECALL | - PROVIDE SPLASH BLOCKS AT GUTTER DOWNSPOUTS - POP OFF DRAIN NOT RAN FROM WATER HEATER - ATTIC PULL DOWN NEEDS TO BE INSTALLED WITH 16D NAILS OR 1/4X3 INCH LAGS PER MANUFACTURED INSTRUCTIONS - SEAL HOLE ON TOP PLATE OVER PANEL - CABLE RAN ON DECKING IN ATTIC NEEDS TO BE REROUTED BENEATH DECKING OR HAVE PERMANENT PROTECTION INSTALLED OVER IT - vent hood connection cannot be made with flex duct has to be hard pipe - anti-tilt device with not installed or not installed properly on oven - need to see passing blower door certificate |
| 05/22/2026 | PERMANENT POWER | Tyler Adams | PASS | — |
| 05/15/2026 | INSULATION | Tyler Adams | PASS | — |