Permit Timeline
In Review
2/18/2026
Issued
COMBINATION ROUGH
05/15/2026
C&R
COMBINATION ROUGH
05/20/2026
PASS
INSULATION
05/22/2026
C&R
INSULATION
05/27/2026
PASS
PERMANENT POWER
06/18/2026
PASS
PERMANENT POWER
06/22/2026
PASS
FINAL
07/07/2026
C&R
FINAL
07/08/2026
PASS
Permit Finaled
7/8/2026
Certificate Issued
10/26/2026
Project Information
Edmunds #
P-480226
MC #
MC2026-110
Issued Date
—
Finaled Date
7/8/2026
Owner
CODY EUGENE KELLY
Owner Address
395 COUNTRY KITCHEN RD, BARNESVILLE, GA 30204
Contractor
AMERICA'S HOME PLACE
Project Type
NEW SINGLE FAMILY RESIDENTIAL
Description
NEW SFR
Technical Details
Construction Type
V-B
Occupancy Group
R-3
Occupant Load
N/A
Square Footage
4229
Zoning
A-R
Sprinklers
NO
APN
073031D
Limitations
NONE
Inspection History
| Date | Type | Inspector | Result | Notes |
|---|---|---|---|---|
| 07/08/2026 | FINAL | Tyler Adams | PASS | — |
| 07/07/2026 | FINAL | Tyler Adams | CORRECT AND RECALL | - label condensers in to match the labels in the panel - porch posts need to be set on brackets - smaller condenser has a maximum breaker rating at 15 amps a 20 amp breaker is installed - water heater is not connected - all outlets in garage require gfci protection - service panel not installed on smaller air handler in attic - seal laundry sink to wall |
| 06/22/2026 | PERMANENT POWER | Tyler Adams | PASS | — |
| 06/18/2026 | PERMANENT POWER | Tyler Adams | PASS | — |
| 05/27/2026 | INSULATION | Tyler Adams | PASS | — |
| 05/22/2026 | INSULATION | Tyler Adams | CORRECT AND RECALL | INSULATION INSTALLATION INCOMPLETE AT TIME OF INSPECTION |
| 05/20/2026 | COMBINATION ROUGH | Tyler Adams | PASS | — |
| 05/15/2026 | COMBINATION ROUGH | Tyler Adams | CORRECT AND RECALL | - check nails guards on the electrical through out - nail guards over dryer vent through studs to exterior - secure CSST gas line in wall - no water on tubs - secure 10-2 cable in ceiling of left master closet - missing sill plate anchors both sides of double doors in living room - missing sill plate anchors both sides of front door - stocked Sheetrock preventing inspection of a few walls - too much deflection in stud hall way by jack and Jill bathroom - missing insulation and vapor barrier behind tub insert of thirds bathroom back right side of house |