198 E WATSON RD

FINALED
NEW SINGLE FAMILY RESIDENTIAL

Permit Timeline

In Review 2/18/2026
Issued
COMBINATION ROUGH 05/15/2026 C&R
COMBINATION ROUGH 05/20/2026 PASS
INSULATION 05/22/2026 C&R
INSULATION 05/27/2026 PASS
PERMANENT POWER 06/18/2026 PASS
PERMANENT POWER 06/22/2026 PASS
FINAL 07/07/2026 C&R
FINAL 07/08/2026 PASS
Permit Finaled 7/8/2026
Certificate Issued 10/26/2026

Project Information

Edmunds #

P-480226

MC #

MC2026-110

Issued Date

—

Finaled Date

7/8/2026

Owner

CODY EUGENE KELLY

Owner Address

395 COUNTRY KITCHEN RD, BARNESVILLE, GA 30204

Contractor

AMERICA'S HOME PLACE

Project Type

NEW SINGLE FAMILY RESIDENTIAL

Description

NEW SFR

Technical Details

Construction Type

V-B

Occupancy Group

R-3

Occupant Load

N/A

Square Footage

4229

Zoning

A-R

Sprinklers

NO

APN

073031D

Limitations

NONE

Inspection History

Date Type Inspector Result Notes
07/08/2026 FINAL Tyler Adams PASS —
07/07/2026 FINAL Tyler Adams CORRECT AND RECALL - label condensers in to match the labels in the panel - porch posts need to be set on brackets - smaller condenser has a maximum breaker rating at 15 amps a 20 amp breaker is installed - water heater is not connected - all outlets in garage require gfci protection - service panel not installed on smaller air handler in attic - seal laundry sink to wall
06/22/2026 PERMANENT POWER Tyler Adams PASS —
06/18/2026 PERMANENT POWER Tyler Adams PASS —
05/27/2026 INSULATION Tyler Adams PASS —
05/22/2026 INSULATION Tyler Adams CORRECT AND RECALL INSULATION INSTALLATION INCOMPLETE AT TIME OF INSPECTION
05/20/2026 COMBINATION ROUGH Tyler Adams PASS —
05/15/2026 COMBINATION ROUGH Tyler Adams CORRECT AND RECALL - check nails guards on the electrical through out - nail guards over dryer vent through studs to exterior - secure CSST gas line in wall - no water on tubs - secure 10-2 cable in ceiling of left master closet - missing sill plate anchors both sides of double doors in living room - missing sill plate anchors both sides of front door - stocked Sheetrock preventing inspection of a few walls - too much deflection in stud hall way by jack and Jill bathroom - missing insulation and vapor barrier behind tub insert of thirds bathroom back right side of house